| Application | 
|---|
| Application | totaliser function; empty pipe detection; for industrial applications | 
| Installation | connection to pipe by means of an adapter | 
| Media | conductive liquids; water; hydrous media | 
| Note on media | | conductivity: ≥ 20 µS/cm |  | viscosity: < 70 mm²/s (40 °C) |  
  | 
| Medium temperature [°F] | 14...158 | 
| Pressure rating [bar] | 16 | 
| Pressure rating [psi] | 232 | 
| MAWP (for applications according to CRN) [bar] | 16.5 | 
| Electrical data | 
|---|
| Operating voltage [V] | 18...32 DC; (according to EN 50178 SELV/PELV) | 
| Current consumption [mA] | < 150 | 
| Protection class | III | 
| Reverse polarity protection | yes | 
| Power-on delay time [s] | 5 | 
| Inputs / outputs | 
|---|
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | 
| Inputs | 
|---|
| Inputs | counter reset | 
| Outputs | 
|---|
| Total number of outputs | 2 | 
| Output signal | switching signal; analogue signal; pulse signal; frequency signal; IO-Link; (configurable) | 
| Electrical design | PNP/NPN | 
| Number of digital outputs | 2 | 
| Output function | normally open / normally closed; (parameterisable) | 
| Max. voltage drop switching output DC [V] | 2 | 
| Permanent current rating of switching output DC [mA] | 250; (per output) | 
| Number of analogue outputs | 1 | 
| Analogue current output [mA] | 4...20; (scalable) | 
| Max. load [Ω] | 500 | 
| Analogue voltage output [V] | 0...10; (scalable) | 
| Min. load resistance [Ω] | 2000 | 
| Pulse output | flow rate meter | 
| Short-circuit protection | yes | 
| Type of short-circuit protection | pulsed | 
| Overload protection | yes | 
| Frequency of the output [Hz] | 0.1...10000 | 
| Measuring/setting range | 
|---|
| Measuring range | | 80...9600 gph | 1.3...160 gpm |  
  | 
| Display range | | -11520...11520 gph | -190...190 gpm |  
  | 
| Resolution |  | 
| Set point SP | | 130...9600 gph | 2.1...160 gpm |  
  | 
| Reset point rP | | 80...9550 gph | 1.3...159.2 gpm |  
  | 
| Analogue start point ASP |  | 
| Analogue end point AEP | | 1920...9600 gph | 32...160 gpm |  
  | 
| Low flow cut-off LFC |  | 
| In steps of |  | 
| Measuring dynamics | 1:120 | 
| Volumetric flow quantity monitoring | 
|---|
| Pulse value | 0.02...160 E06 gal | 
| In steps of | 0.02 gal | 
| Pulse length [s] | 0,008...2 | 
| Software / programming | 
|---|
| Parameter setting options | Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/frequency/pulse output; start-up delay; display can be deactivated; Display unit; empty pipe detection | 
| Operating conditions | 
|---|
| Ambient temperature [°F] | 14...140 | 
| Storage temperature [°F] | -13...176 | 
| Protection | IP 65; IP 67 | 
| Mechanical data | 
|---|
| Weight [g] | 3175.15 | 
| Materials | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U | 
| Materials (wetted parts) | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Centellen; FKM | 
| Process connection | threaded connection G 2 DN50 flat seal | 
| Displays / operating elements | 
|---|
| Display | | Display unit | 6 x LED, green (gpm, gph, gal, °F, 10³, 1000 x 10³) |  | switching status | 2 x LED, yellow |  | measured values | alphanumeric display, 4-digit |  | programming | alphanumeric display, 4-digit |  
  | 
| Electrical connection | 
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |