Instrumentation

HOT

SA4100

9,224,704 VND

Application
Mediawater; glycol solutions; air; oils
Note on media
low-viscosity oils with viscosity: ≤ 40 mm²/s (40 °C)
high-viscosity oils with viscosity: > 40 mm²/s (40 °C)
Medium temperature [°C]-20...100
Pressure rating [bar]50
MAWP (for applications according to CRN) [bar]50
Electrical data
Operating voltage [V]18...30 DC
Current consumption [mA]< 100
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs2
Output signalswitching signal; analogue signal; frequency signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2.5
Permanent current rating of switching output DC [mA]250
Number of analogue outputs1
Analogue current output [mA]4...20; (scalable)
Max. load [Ω]350
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Frequency of the output [Hz]0...1000
Measuring/setting range
Probe length L [mm]100
Operating moderelative; absolutely liquid; absolutely gaseous
Note on setting range
Operating mode: relative
Liquids
Measuring range [m/s]0.04...3
Setting range [m/s]0...6
Gases
Measuring range [m/s]2...100
Setting range [m/s]0...200
Temperature monitoring
Measuring range [°C]-20...100
Resolution [°C]0.2
Software / programming
Parameter setting optionshysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour
Operating conditions
Ambient temperature [°C]-40...80
Storage temperature [°C]-40...100
ProtectionIP 65; IP 67
Mechanical data
Weight [g]299.5
Materialsstainless steel (1.4404 / 316L); PBT-GF20; PBT-GF30
Materials (wetted parts)stainless steel (1.4404 / 316L)
Process connectiondiameter Ø 8 mm
Displays / operating elements
Display
Display unit6 x LED, green (%, m/s, l/min, m³/h, °C, 10³)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Electrical connection
ConnectionConnector: 1 x M12; Contacts: gold-plated
Buy
HOT

SA5000

8,898,638 VND

Application
Mediawater; glycol solutions; air; oils
Note on media
low-viscosity oils with viscosity: ≤ 40 mm²/s (40 °C)
high-viscosity oils with viscosity: > 40 mm²/s (40 °C)
Medium temperature [°C]-20...90
Pressure rating [bar]100
MAWP (for applications according to CRN) [bar]100
Electrical data
Operating voltage [V]18...30 DC
Current consumption [mA]< 100
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs2
Output signalswitching signal; analogue signal; frequency signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2.5
Permanent current rating of switching output DC [mA]250
Number of analogue outputs1
Analogue current output [mA]4...20; (scalable)
Max. load [Ω]350
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Frequency of the output [Hz]0...1000
Measuring/setting range
Probe length L [mm]45
Operating moderelative; absolutely liquid; absolutely gaseous
Note on setting range
Operating mode: relative
Liquids
Measuring range [m/s]0.04...3
Setting range [m/s]0...6
Gases
Measuring range [m/s]2...100
Setting range [m/s]0...200
Temperature monitoring
Measuring range [°C]-20...90
Resolution [°C]0.2
Software / programming
Parameter setting optionshysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour
Operating conditions
Ambient temperature [°C]-40...80
Storage temperature [°C]-40...100
ProtectionIP 65; IP 67
Mechanical data
Weight [g]311.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PBT-GF20; PBT-GF30
Materials (wetted parts)stainless steel (1.4404 / 316L); Gasket: FKM
Process connectionthreaded connection M18 x 1,5 internal thread
Displays / operating elements
Display
Display unit6 x LED, green (%, m/s, l/min, m³/h, °C, 10³)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Electrical connection
ConnectionConnector: 1 x M12; Contacts: gold-plated
Buy
HOT

SI5000

8,542,929 VND

Application
MediaLiquids; Gases
Medium temperature [°C]-25...80
Pressure rating [bar]30
Liquids
Medium temperature [°C]-25...80
Gases
Medium temperature [°C]-25...80
Electrical data
Operating voltage [V]19...36 DC
Current consumption [mA]< 60
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 1
Outputs
Total number of outputs1
Output signalswitching signal
Electrical designPNP
Number of digital outputs1
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2.5
Permanent current rating of switching output DC [mA]250
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Measuring/setting range
Probe length L [mm]45
Liquids
Setting range [cm/s]3...300
Greatest sensitivity [cm/s]3...100
Gases
Setting range [cm/s]200...3000
Greatest sensitivity [cm/s]200...800
Software / programming
Adjustment of the switch pointpushbutton
Operating conditions
Ambient temperature [°C]-25...80
Storage temperature [°C]-25...100
ProtectionIP 67
Mechanical data
Weight [g]246
Dimensions [mm]M18 x 1.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PC; PBT-GF20; EPDM/X
Materials (wetted parts)stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A
Process connectionM18 x 1,5 internal thread
Displays / operating elements
Display
function10 x LED, three-colour
Electrical connection
ConnectionConnector: 1 x M12
Buy
HOT

SI5004

8,498,466 VND

Application
MediaLiquids
Medium temperature [°C]-25...80
Pressure rating [bar]300
MAWP (for applications according to CRN) [bar]208
Electrical data
Operating voltage [V]19...36 DC
Current consumption [mA]< 60
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of analogue outputs: 1
Outputs
Total number of outputs1
Output signalanalogue signal
Number of analogue outputs1
Analogue current output [mA]4...20
Max. load [Ω]500
Overload protectionyes
Measuring/setting range
Liquids
Setting range [cm/s]3...300
Greatest sensitivity [cm/s]3...100
Operating conditions
Ambient temperature [°C]-25...80
Storage temperature [°C]-25...100
ProtectionIP 67
Mechanical data
Weight [g]248
Dimensions [mm]M18 x 1.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X
Materials (wetted parts)stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A
Process connectionM18 x 1,5 internal thread
Displays / operating elements
Display
function10 x LED, three-colour
Electrical connection
ConnectionConnector: 1 x M12
Buy
HOT

SI5006

9,461,843 VND

Application
MediaLiquids; Gases
Medium temperature [°C]-25...80
Pressure rating [bar]300
MAWP (for applications according to CRN) [bar]208
Liquids
Medium temperature [°C]-25...80
Gases
Medium temperature [°C]-25...80
Electrical data
Operating voltage tolerance [%]-5...10
Operating voltage [V]85...265 AC
Nominal voltage AC [V]90...240
Nominal frequency AC [Hz]50...60
Max. power consumption [VA]3.5
Protection classII
Reverse polarity protectionno
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 1
Outputs
Total number of outputs1
Output signalswitching signal
Electrical designrelay
Number of digital outputs1
Output functionnormally open / normally closed; (parameterisable)
Contact rating3 A (250 V AC / 30 V DC); (number of switching cycles: 20 million mechanically; switching cycles at 3 A load: 100,000 electrical; type of switch-off: normally open)
Short-circuit proofno
Overload protectionno
Measuring/setting range
Liquids
Setting range [cm/s]3...300
Greatest sensitivity [cm/s]3...100
Gases
Setting range [cm/s]200...3000
Greatest sensitivity [cm/s]200...800
Software / programming
Adjustment of the switch pointpushbutton
Operating conditions
Ambient temperature [°C]-25...80
Storage temperature [°C]-25...100
ProtectionIP 67
Mechanical data
Weight [g]262.5
Dimensions [mm]M18 x 1.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X
Materials (wetted parts)stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A
Process connectionM18 x 1,5 internal thread
Displays / operating elements
Display
function10 x LED, three-colour
Electrical connection
ConnectionConnector: 1 x 1/2"
Buy
HOT

SI5010

9,034,993 VND

Application
MediaLiquids; Gases
Medium temperature [°C]-25...80
Pressure rating [bar]300
MAWP (for applications according to CRN) [bar]208
Liquids
Medium temperature [°C]-25...80
Gases
Medium temperature [°C]-25...80
Electrical data
Operating voltage [V]18...36 DC
Current consumption [mA]< 60
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 1
Outputs
Total number of outputs1
Output signalswitching signal; IO-Link; (configurable)
Electrical designPNP
Number of digital outputs1
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2.5
Permanent current rating of switching output DC [mA]250
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Measuring/setting range
Liquids
Setting range [cm/s]3...300
Greatest sensitivity [cm/s]3...100
Gases
Setting range [cm/s]200...3000
Greatest sensitivity [cm/s]200...800
Software / programming
Adjustment of the switch pointpushbutton
Operating conditions
Ambient temperature [°C]-25...80
Storage temperature [°C]-25...100
ProtectionIP 65; IP 67
Mechanical data
Weight [g]248.5
Dimensions [mm]M18 x 1.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X
Materials (wetted parts)stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A
Process connectionM18 x 1,5 internal thread
Displays / operating elements
Display
function10 x LED, three-colour
Electrical connection
ConnectionConnector: 1 x M12
Buy

SR5906

7,040,061 VND

Application
ApplicationFlow monitoring; Wire monitoring
Electrical data
Operating voltage tolerance [%]-15...10
Operating voltage [V]76.5...264 AC
Nominal voltage AC [V]90...240
Nominal frequency AC [Hz]50...60
Max. power consumption [VA]3.5
Protection classII
Reverse polarity protectionno
Power-on delay time [s]10
Number of channels1
Outputs
Electrical designrelay
Contact rating3 A (250 V AC / 30 V DC); (switching cycles at 3 A load: 100.000; type of switch-off: normally open)
Switching cycles (mechanical)20_Millionen
Switching function flow monitoringoutput switches when flow is present: ON for output function = normally open / OFF for output function = normally closed
Short-circuit protectionno
Overload protectionno
Software / programming
Adjustment of the switch pointpushbutton
Operating conditions
Ambient temperature [°C]-20...60
ProtectionIP 67; (with sensor attached)
Mechanical data
Weight [g]244.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X; brass
Displays / operating elements
Display
functionLED, bar graph
switching statusLED, orange flash in case of wire break
Electrical connection
ConnectionConnector: 1 x 1/2"
Buy

SR5900

6,435,358 VND

Application
ApplicationFlow monitoring; Wire monitoring
Electrical data
Operating voltage [V]19...36 DC
Current consumption [mA]< 70
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Number of channels1
Outputs
Electrical designPNP
Max. voltage drop switching output DC [V]2.5
Permanent current rating of switching output DC [mA]250
Switching function flow monitoringoutput switches when flow is present: ON for output function = normally open / OFF for output function = normally closed
Short-circuit protectionyes
Overload protectionyes
Software / programming
Adjustment of the switch pointpushbutton
Operating conditions
Ambient temperature [°C]-20...60
ProtectionIP 67; (with sensor attached)
Mechanical data
Weight [g]225.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X; brass
Displays / operating elements
Display
functionLED, bar graph
switching statusLED, orange flash in case of wire break
Electrical connection
ConnectionConnector: 1 x M12
Buy

LDL100

15,854,067 VND

Application
Mediaconductive liquids
Note on media
water
milk
CIP liquids
Medium temperature [°C]-25...100; (< 1 h: 150)
Tank pressure [bar]-1...16
Electrical data
Operating voltage [V]18...30 DC
Current consumption [mA]< 60
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]2
Inputs / outputs
Number of inputs and outputsNumber of analogue outputs: 1
Outputs
Total number of outputs1
Output signalanalogue signal; IO-Link
Output functionanalogue output; scalable; selectable conductivity / temperature
Number of analogue outputs1
Analogue current output [mA]4...20
Max. load [Ω]500
Measuring/setting range
Conductivity measurement
Measuring range [µS/cm]100...15000
Temperature measurement
Measuring range [°C]-25...150
Temperature measurement
Response time [s]< 9; (T09)
Operating conditions
Ambient temperature [°C]-40...60
Storage temperature [°C]-40...85
ProtectionIP 68; IP 69K; (IP 68: 7 days / 3 m water depth / 0.3 bar)
Mechanical data
Weight [g]270.5
Materialsstainless steel (1.4404 / 316L); PEEK; PEI; FKM
Materials (wetted parts)PEEK; stainless steel (1.4404 / 316L)
Process connectionG 1/2 external thread
Electrical connection
ConnectionConnector: 1 x M12 (EN 61067-2-101); Contacts: gold-plated
Buy

LDL200

31,708,133 VND

Application
Mediaconductive liquids
Note on media
water
milk
CIP liquids
Medium temperature [°C]-25...100; (< 1 h: 150)
Tank pressure [bar]-1...16
Electrical data
Operating voltage [V]18...30 DC
Current consumption [mA]< 70
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]2
Inputs / outputs
Number of inputs and outputsNumber of analogue outputs: 1
Outputs
Total number of outputs1
Output signalanalogue signal; IO-Link
Output functionanalogue output; scalable; selectable conductivity / temperature
Number of analogue outputs1
Analogue current output [mA]4...20
Max. load [Ω]500
Measuring/setting range
Conductivity measurement
Measuring range [µS/cm]100...1000000
Temperature measurement
Measuring range [°C]-25...150
Conductivity measurement
Accuracy (in the measuring range)2 % MW ± 25 µS/cm
Resolution [µS/cm]1
Drift [%/K]0,1 %/K MW ± 25 µS/cm
Repeatability1 % MW ± 25 µS/cm
Long-term stability0,5 % MW ± 25 µS/cm
Operating conditions
Ambient temperature [°C]-40...60
Storage temperature [°C]-40...85
ProtectionIP 68; IP 69K; (IP 68: 7 days / 3 m water depth / 0.3 bar)
Mechanical data
Weight [g]580.5
Materialsstainless steel (1.4404 / 316L); PEEK; PEI; FKM
Materials (wetted parts)PEEK
Process connectionG 1 external thread Aseptoflex Vario
Electrical connection
ConnectionConnector: 1 x M12 (EN 61067-2-101); Contacts: gold-plated
Buy

SM0510

29,491,189 VND

Application
Applicationtotaliser function; empty pipe detection; for industrial applications
Installationconnection to pipe by means of an adapter
Mediaconductive liquids; water; hydrous media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C]-10...70
Pressure rating [bar]16
Electrical data
Operating voltage [V]18...32 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]< 150
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]5
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputscounter reset
Outputs
Total number of outputs2
Output signalswitching signal; analogue signal; pulse signal; frequency signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2
Permanent current rating of switching output DC [mA]250; (per output)
Number of analogue outputs1
Analogue current output [mA]4...20; (scalable)
Max. load [Ω]500
Analogue voltage output [V]0...10; (scalable)
Min. load resistance [Ω]2000
Pulse outputflow rate meter
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Frequency of the output [Hz]0.1...10000
Measuring/setting range
Measuring range
5...900 l/min0.3...54 m³/h
Display range
-920...920 l/min-55.2...55.2 m³/h
Resolution
1 l/min0.05 m³/h
Set point SP
10...900 l/min0.55...54 m³/h
Reset point rP
5...896 l/min0.3...53.75 m³/h
Analogue start point ASP
0...720 l/min0...43.2 m³/h
Analogue end point AEP
180...900 l/min10.8...54 m³/h
Low flow cut-off LFC
< 15 l/min< 0.9 m³/h
In steps of
1 l/min0.05 m³/h
Measuring dynamics1:180
Volumetric flow quantity monitoring
Pulse value0.1 l...600 x 10³ m³
In steps of0.1 l
Pulse length [s]0,003...2
Temperature monitoring
Measuring range [°C]-20...80
Display range [°C]-40...100
Resolution [°C]0.2
Set point SP [°C]-19.2...80
Reset point rP [°C]-19.6...79.6
Analogue start point [°C]-20...60
Analogue end point [°C]0...80
In steps of [°C]0.2
Software / programming
Parameter setting optionsFlow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/frequency/pulse output; start-up delay; display can be deactivated; Display unit; empty pipe detection
Operating conditions
Ambient temperature [°C]-10...60
Storage temperature [°C]-25...80
ProtectionIP 65; IP 67
Mechanical data
Weight [g]3212
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PC; FKM; PBT-GF20; TPE-U
Materials (wetted parts)stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Hastelloy C-4 (2.4610); Centellen; FKM
Process connectionthreaded connection G 2 DN50 flat seal
Displays / operating elements
Display
Display unit6 x LED, green (l/min, m³/h, l, m³, 10³, °C)
switching status2 x LED, yellow
measured valuesalphanumeric display, 4-digit
programmingalphanumeric display, 4-digit
Electrical connection
ConnectionConnector: 1 x M12; Contacts: gold-plated
Buy

SM4000

16,226,231 VND

Application
Applicationtotaliser function; for industrial applications
Installationconnection to pipe by means of an adapter
Mediaconductive liquids; water; hydrous media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C]0...60
Pressure rating [bar]10
MAWP (for applications according to CRN) [bar]7.3
Electrical data
Operating voltage [V]18...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]< 80
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]5
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputscounter reset
Outputs
Total number of outputs2
Output signalswitching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2
Permanent current rating of switching output DC [mA]200
Number of analogue outputs1
Analogue current output [mA]4...20; (scalable)
Max. load [Ω]500
Analogue voltage output [V]0...10; (scalable)
Min. load resistance [Ω]2000
Pulse outputflow rate meter
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Measuring/setting range
Measuring range [ml/min]5...3000
Display range [ml/min]-1999...3600
Resolution [ml/min]1
Set point SP [ml/min]20...3000
Reset point rP [ml/min]5...2984
Analogue start point ASP [ml/min]0...2400
Analogue end point AEP [ml/min]600...3000
Low flow cut-off LFC [ml/min]< 60
Volumetric flow quantity monitoring
Pulse value0.001...3000 l
Pulse length [s]0,008...2
Software / programming
Parameter setting optionsFlow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/pulse output; start-up delay; display can be deactivated; Display unit
Operating conditions
Ambient temperature [°C]-10...60
Storage temperature [°C]-25...80
ProtectionIP 67
Mechanical data
Weight [g]536.5
Materialsstainless steel (1.4404 / 316L); PBT-GF20; PC; FKM; TPE
Materials (wetted parts)stainless steel (1.4404 / 316L); PEEK; FKM
Process connectionthreaded connection G 1/4 DN6 flat seal
Displays / operating elements
Display
Display unit6 x LED, green (ml/min, l/h, l, m³, °C, 10³)
switching status2 x LED, yellow
measured valuesalphanumeric display, 4-digit
programmingalphanumeric display, 4-digit
Electrical connection
ConnectionConnector: 1 x M12; Contacts: gold-plated
Buy