SI5004

8,498,466 ₫

Application
MediaLiquids
Medium temperature [°C]-25...80
Pressure rating [bar]300
MAWP (for applications according to CRN) [bar]208
Electrical data
Operating voltage [V]19...36 DC
Current consumption [mA]< 60
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]10
Inputs / outputs
Number of inputs and outputsNumber of analogue outputs: 1
Outputs
Total number of outputs1
Output signalanalogue signal
Number of analogue outputs1
Analogue current output [mA]4...20
Max. load [Ω]500
Overload protectionyes
Measuring/setting range
Liquids
Setting range [cm/s]3...300
Greatest sensitivity [cm/s]3...100
Operating conditions
Ambient temperature [°C]-25...80
Storage temperature [°C]-25...100
ProtectionIP 67
Mechanical data
Weight [g]248
Dimensions [mm]M18 x 1.5
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X
Materials (wetted parts)stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A
Process connectionM18 x 1,5 internal thread
Displays / operating elements
Display
function10 x LED, three-colour
Electrical connection
ConnectionConnector: 1 x M12

 