HOT

SM2000

28,545,597 ₫

Application
Applicationtotaliser function; empty pipe detection; for industrial applications
Installationconnection to pipe by means of an adapter
Mediaconductive liquids; water; hydrous media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C]-10...70
Pressure rating [bar]16
MAWP (for applications according to CRN) [bar]16.5
Electrical data
Operating voltage [V]18...32 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]< 150
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]5
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputscounter reset
Outputs
Total number of outputs2
Output signalswitching signal; analogue signal; pulse signal; frequency signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]2
Permanent current rating of switching output DC [mA]250; (per output)
Number of analogue outputs1
Analogue current output [mA]4...20; (scalable)
Max. load [Ω]500
Analogue voltage output [V]0...10; (scalable)
Min. load resistance [Ω]2000
Pulse outputflow rate meter
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Frequency of the output [Hz]0.1...10000
Measuring/setting range
Measuring range
5...600 l/min0.3...36 m³/h
Display range
-720...720 l/min-43.2...43.2 m³/h
Resolution
0.5 l/min0.02 m³/h
Set point SP
8...600 l/min0.5...36 m³/h
Reset point rP
5...597 l/min0.3...35.8 m³/h
Analogue start point ASP
0...480 l/min0...28.8 m³/h
Analogue end point AEP
120...600 l/min7.2...36 m³/h
Low flow cut-off LFC
< 15 l/min< 0.9 m³/h
In steps of
0.5 l/min0.02 m³/h
Measuring dynamics1:120
Volumetric flow quantity monitoring
Pulse value0.0001...600x10³ m³
In steps of0.0001 m³
Pulse length [s]0,008...2
Temperature monitoring
Measuring range [°C]-20...80
Display range [°C]-40...100
Resolution [°C]0.2
Set point SP [°C]-19.2...80
Reset point rP [°C]-19.6...79.6
Analogue start point [°C]-20...60
Analogue end point [°C]0...80
In steps of [°C]0.2
Software / programming
Parameter setting optionsFlow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/frequency/pulse output; start-up delay; display can be deactivated; Display unit; empty pipe detection
Operating conditions
Ambient temperature [°C]-10...60
Storage temperature [°C]-25...80
ProtectionIP 65; IP 67
Mechanical data
Weight [g]3178
Materialsstainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U
Materials (wetted parts)stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Centellen; FKM
Process connectionthreaded connection G 2 DN50 flat seal
Displays / operating elements
Display
Display unit6 x LED, green (l/min, m³/h, l, m³, 10³, °C)
switching status2 x LED, yellow
measured valuesalphanumeric display, 4-digit
programmingalphanumeric display, 4-digit
Accessories
Accessories (supplied)
sealings: 2, Centellen
Label
Electrical connection
ConnectionConnector: 1 x M12; Contacts: gold-plated

 

Mua hàng