| Application | 
|---|
| Application | totaliser function; for industrial applications | 
| Installation | connection to pipe by means of an adapter | 
| Media | conductive liquids; water; hydrous media | 
| Note on media | | conductivity: ≥ 20 µS/cm |  | viscosity: < 70 mm²/s (40 °C) | 
 | 
| Medium temperature [°C] | -10...70 | 
| Pressure rating [bar] | 16 | 
| MAWP (for applications according to CRN) [bar] | 11.2 | 
| Electrical data | 
|---|
| Operating voltage [V] | 18...30 DC; (according to EN 50178 SELV/PELV) | 
| Current consumption [mA] | 95; (24 V) | 
| Protection class | III | 
| Reverse polarity protection | yes | 
| Power-on delay time [s] | 5 | 
| Inputs / outputs | 
|---|
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | 
| Inputs | 
|---|
| Inputs | counter reset | 
| Outputs | 
|---|
| Total number of outputs | 2 | 
| Output signal | switching signal; analogue signal; pulse signal; IO-Link; (configurable) | 
| Electrical design | PNP/NPN | 
| Number of digital outputs | 2 | 
| Output function | normally open / normally closed; (parameterisable) | 
| Max. voltage drop switching output DC [V] | 2 | 
| Permanent current rating of switching output DC [mA] | 200 | 
| Number of analogue outputs | 1 | 
| Analogue current output [mA] | 4...20; (scalable) | 
| Max. load [Ω] | 500 | 
| Analogue voltage output [V] | 0...10; (scalable) | 
| Min. load resistance [Ω] | 2000 | 
| Pulse output | flow rate meter | 
| Short-circuit protection | yes | 
| Type of short-circuit protection | pulsed | 
| Overload protection | yes | 
| Measuring/setting range | 
|---|
| Measuring range | | 0.2...100 l/min | 0.01...6 m³/h | 
 | 
| Display range | | -120...120 l/min | -7.2...7.2 m³/h | 
 | 
| Resolution |  | 
| Set point SP | | 0.7...100 l/min | 0.04...6 m³/h | 
 | 
| Reset point rP | | 0.2...99.5 l/min | 0.01...5.97 m³/h | 
 | 
| Analogue start point ASP |  | 
| Analogue end point AEP | | 20...100 l/min | 1.2...6 m³/h | 
 | 
| In steps of |  | 
| Volumetric flow quantity monitoring | 
|---|
| Pulse value | 0.00001...100 000 m³ | 
| Pulse length [s] | 0,0025...2 | 
| Software / programming | 
|---|
| Parameter setting options | Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/pulse output; start-up delay; display can be deactivated; Display unit | 
| Operating conditions | 
|---|
| Ambient temperature [°C] | -10...60 | 
| Storage temperature [°C] | -25...80 | 
| Protection | IP 67 | 
| Mechanical data | 
|---|
| Weight [g] | 639.5 | 
| Materials | stainless steel (1.4404 / 316L); PBT-GF20; PC; FKM; TPE | 
| Materials (wetted parts) | stainless steel (1.4404 / 316L); PEEK; EPDM | 
| Process connection | threaded connection G 1 DN25 flat seal | 
| Displays / operating elements | 
|---|
| Display | | Display unit | 6 x LED, green (l/min, m³/h, l, m³, 10³, °C) |  | switching status | 2 x LED, yellow |  | measured values | alphanumeric display, 4-digit |  | programming | alphanumeric display, 4-digit | 
 | 
| Electrical connection | 
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |