| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | 
| Output signal | Switching signal; analogue signal; IO-Link; (configurable) | 
| Electrical design | PNP/NPN | 
| Number of digital outputs | 2 | 
| Output function           | Normally open / normally closed; (parameterisable) | 
| Number of analogue outputs   | 1 | 
| Analogue current output [mA] | 4...20, invertible; (scalable) | 
| Short-circuit protection            | Yes | 
| Type of short-circuit protection           | Pulsed | 
| Overload protection | Yes | 
| Measuring range | -0.05...1 bar     -50...1000 mbar          -0.73...14.5 psi | 
| Application      | Hygienic systems | 
| Media  | Viscous media and liquids with suspended particles; liquids and gases | 
| Medium temperature [°C] | -25...125; (145 max. 1h) | 
| Pressure rating | 10000 mbar     145 psi | 
| Min. bursting pressure | 30000 mbar     435 psi | 
| Vacuum resistance [mbar] | -1000 | 
| Type of pressure | Relative pressure | 
| No dead space | Yes | 
| Min. insulation resistance [MΩ]           | 100; (500 V DC) | 
| Protection class            | III | 
| Reverse polarity protection | Yes | 
| Integrated watchdog | Yes | 
| 2-wire | Operating voltage [V] | 20...32 DC | 
| Current consumption [mA]      | 3.6...21 | 
| Power-on delay time [s]                                   | 1 | 
| Max. load [Ω]  | 300 | 
| Step response time analogue output [ms]         | 45 | 
| 3-wire | Operating voltage [V]  | 18...32 DC | 
| Current consumption [mA]      | < 45 | 
| Power-on delay time [s]           | 0.5 | 
| Max. voltage drop switching output DC [V]    | 2 | 
| Permanent current rating of switching output DC [mA] | 250 | 
| Switching frequency DC [Hz]  | 125 | 
| Max. load [Ω]  | (Ub - 10 V) / 20 mA | 
| Min. response time of switching output (dAP) [ms] | 3 | 
| Step response time analogue output [ms]         | 7 | 
| Measuring range          | -0.05...1 bar              -50...1000 mbar            -0.73...14.5 psi | 
| Set point SP | -48...1000 mbar                       -0.7...14.5 psi | 
| Reset point rP  | -50...998 mbar         -0.73...14.47 psi | 
| Analogue start point                 | -50...750 mbar         -0.73...10.88 psi | 
| Analogue end point                             | 200...1000 mbar          2.9...14.5 psi | 
| In steps of                    | 1 mbar 0.01 psi | 
| Response times | Damping for the switching output dAP [s] | 0...30 | 
| Damping for the analogue output dAA [s] | 0.01...99.99 | 
| Ambient temperature [°C]                                            | -25...80 | 
| Storage temperature [°C]                                              | -40...100 | 
| Protection        | IP 67; IP 68; IP 69K | 
| Weight [g]        | 356 | 
| Materials | Stainless steel (1.4404 / 316L); FKM; PTFE; PBT; PEI; PFA | 
| Materials (wetted parts)                                                                        | Ceramics (99.9 % Al2O3); PTFE; stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4 | 
| Display            | Display unit                                         | LED, green | 
| Switching status | LED, yellow | 
| Function display | Alphanumeric display, 4-digit | 
| Measured values          | Alphanumeric display, 4-digit | 
| Display unit     | mbar; kPa; psi; inH2O; mWS; % of the span | 
| Process connection      | Threaded connection G 1 external thread Aseptoflex Vario | 
| Connection | Connector: 1 x M12; Contacts: gold-plated |